GFB1L-63NH Electronic Residual Current Circuit Breaker (3P+N Longbody) RCBO
GFB1L-63NH Residual Current Breaker RCBO 10kA 3 Pole and Neutral 63A C Curve 30mA Type A (Longbody)sidual Current Breaker RCBO 10kA 3 Pole and Neutral 63A C Curve 30mA Type A (Longbody)
GFB1L-63N Range of residual current devices (RCDs) are a high-performance electrical safety solution designed for commercial, industrial and mining applications. These RCDs offer a high level of selectivity, with sensitives including 10mA, 30mA, 100mA,300mA and500mA, types starting at Type A for general purpose applications through to Type F and B for more complex loads.
● Standard: IEC/EN 61009-1
● Type: AC, A
● Rated current: 6A,10A,16A,20A,25A,32A,40A,50A,63A
● Rated voltage: 400/415V~
● Number of poles: 3P+N
● Rated Residual Operating Current (I△n): 10mA, 30mA, 100mA, 300mA,500mA
● Rated short-circuit breaking capacity: 10kA
● Tripping curve: B,C
● Ambient air temperature: -35℃~+70 ºC
● Certificates: CB,CE, UKCA,SEMKO
Product Description
●Model and Meaning ●Introduction
GFB1L-63NH Electronic residual current trip (3P+N) is a low-voltage protection device that integrates overload, short circuit, and leakage protection. Its core feature is the use of electronic trip technology to achieve accurate leakage detection. The following is the key description:
Ⓐ structural property
● Polarity configuration: 3P+N denotes a three-phase (L1/L2/L3) system with a neutral (N) line. The neutral pole is typically used solely for isolation or leakage detection, without overcurrent protection capability.
● Module design: The standard module is 54mm (3×18mm), with the N pole occupying space but not independently separated.
Ⓑ principle of work and power
● Leakage protection: Detects residual current through a zero-sequence current transformer. When the leakage current exceeds the preset threshold (e.g., 30mA), the electronic tripping mechanism activates.
● Wiring requirements: Strictly follow the left neutral, right live principle. The N line must be connected to the terminal marked N. Otherwise, the protection may fail.
Ⓒ application scenarios-Industrial control systems, electrical installations in commercial buildings, and household circuit protection
● Suitable for three-phase four-wire systems (e.g., 380V power equipment) where neutral line leakage detection is required but no neutral line disconnection is needed.
● Common in industrial control, commercial building distribution boxes, etc.
Ⓓ Selection considerations
● Specify the N-pole function requirements (e.g., whether synchronization and disconnection are required)
● Prioritize products compliant with IEC/EN 61009-1 standards, ensuring a breaking capacity of ≥10kA
●Technical Parameters
Product Model | GFB1L-63NH |
Product complies with standard | IEC/EN 61009-1 |
No. of poles | 3P+N |
Rated current (In) | 6A,10A,16A,20A,25A,32A,40A,50A,63A |
Rated sensitivity currents I△n | 10mA, 30mA, 100mA, 300mA,500mA |
Rated short-circuit breaking capacity | 10kA |
Energy limiting class | 3 |
Rated voltage (Ue) | 400/415V |
Rated impulse withstand voltage (1.2/50) Uimp | 4kV |
Trip curve | B、C |
Leakage current type | AC、A |
Tripping time | 300ms |
Min.service voltage | 207V |
Max.operating voltage(Uamx) | 457V |
Protected neutral pole | No |
Isolator application | Yes |
Disconnection characteristic | Undelayed |
Protection | Ground fault, Overcurrent and short circuit |
Type of trip | Ground fault: Electronic |
Overload and short circuit: Thermo-magnetic | |
Residual current off-time under I△n | ≤0.1s |
Reted residual making and breaking capacity (I△m) | 500A(In≤50A) |
Thermal release characteristic | (1.13-1.45) x In |
Magnetic release characteristic | B:(3-5) x In, C:(5-10) x In |
Electrical Life | 10000 Cycles |
Mechanical Life | 20000 Cycles |
Contact Position Indicator | Yes, ON (red); OFF (green) |
Ambient Temperature | -35℃~+70℃, Maximum Humidity 95% |
Datum temperature | 30℃ |
Protection Degree | IP20 |
Connectable conductor cross section solid-core | 1-25mm² |
Connectable conductor cross section multi-wired | 1-16mm² |
Torque (N·m) | -35℃~+70℃, Maximum Humidity 95% |
Installation | 30℃ |
Depth | IP20 |
Height | 1-25mm² |
Width | 1-16mm² |
●Product Types Choosing
| Rated Current | Rated Residual Operation Current(I△n) | Product Number | |
| Type B | Type C | ||
| 6A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB0610 GFB1L-63NHB0630 | GFB1L-63NHC0610 GFB1L-63NHC0630 |
| 10A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB1010 GFB1L-63NHB1030 | GFB1L-63NHC1010 GFB1L-63NHC1030 |
| 16A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB1610 GFB1L-63NHB1630 | GFB1L-63NHC1610 GFB1L-63NHC1630 |
| 20A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB2010 GFB1L-63NHB2030 | GFB1L-63NHC2010 GFB1L-63NHC2030 |
| 25A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB2510 GFB1L-63NHB2530 | GFB1L-63NHC2510 GFB1L-63NHC2530 |
| 32A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB3210 GFB1L-63NHB3230 | GFB1L-63NHC3210 GFB1L-63NHC3230 |
| 40A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB4010 GFB1L-63NHB4030 | GFB1L-63NHC4010 GFB1L-63NHC4030 |
| 50A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB5010 GFB1L-63NHB5030 | GFB1L-63NHC5010 GFB1L-63NHC5030 |
| 63A | 10mA、30mA、100mA、300mA、500mA | GFB1L-63NHB6310 GFB1L-63NHB6330 | GFB1L-63NHC6310 GFB1L-63NHC6330 |
●Connecting Line
Rated current In (A) | Nominal cross-sectional area S (mm²) of copper wire |
6、10 | 1-2.5 |
16 | 2.5-4 |
20、25 | 4-6 |
32、40 | 6-10 |
50、63 | 10-16 |
●Appearance and Installation Dimensions ●Characteristic Curves


Keywords:
Related Products
undefined
Welcome your message consultation
You can also submit information online, and we will reply to you within 24 hours!
Sales support
Yueqing Good Future Electrical Co.,Ltd.
Phone: +86 138 0686 5401
Tel: +86 577 6161 6165
Email : gf@gf-ele.com
No.136-138,Xinguang Avenue,Xinguang lndustrial Zone,Liushi Town
Yueqing City,Wenzhou City,Zhejiang Province,China
Certificate
Copyright © 2024 Yueqing Good Future Electrical Co., Ltd.